Allen Bradley J Serisi Kompakt Şalterler

Circuit Breakers 140UE — 250 A, J-Frame

  • Thermal Magnetic Trip
  • Electronic Trip LS, LSI, LSG and LSIG
  • 25, 40, 70 kA Breaking Capacity @ 415V (50 Hz)
  • 3-pole, 4-pole
    Approvals
  • IEC 60947-2, CE, KEMA-KEUR
  • Product Selection

    40 kA, Assembled Circuit Breakers, Thermal-Magnetic Trip Units

Rated Operational Current (In) Thermal Trip
(
Ir = 0.8…1.0 x In)
Magnetic Trip
(
Im = 5…10 x In)
Breaking Capacity (50 Hz)
Icu /Ics [kA]
3-Pole
[A] [A] [A] 380…415V 500V 690V Cat. No.
80 64…80 400…800 40 40 35 20 12 6 140UE-J4F3-C80
100 80…100 500…1000 40 40 35 20 12 6 140UE-J4F3-D10
125 100…125 625…1250 40 40 35 20 12 6 140UE-J4F3-D12
160 128…160 800…1600 40 40 35 20 12 6 140UE-J4F3-D16
200 160…200 1000…2000 40 40 35 20 12 6 140UE-J4F3-D20
250 200…250 1250…2500 40 40 35 20 12 6 140UE-J4F3-D25

Isolation Disconnector — IEC 60947-3

Rated Operational Current (In) Thermal Trip
(
Ir = 0.8…1.0 x In)
Magnetic Trip
(
Im = 10 x In)
Breaking Capacity (50 Hz)
Icu /Ics [kA]
3-Pole
[A] [A] [A] 380…415V 500V 690V Cat. No.
250 2500 70 70 25 10 14 7 140UE-J7S3-D25